| INPUT |
| Rated power | 3000 VA |
| Voltage | 220 / 230 / 240 V |
| Voltage tolerance | 230 V ±20% |
| Frequency | 50 / 60 Hz |
| Frequency tolerance | 50 Hz ±5% / 60 Hz ±5% |
| Power factor | >0.99 |
| Current distorsion | ≤7% |
| BY PASS |
| Voltage tolerance | 180 / 264 V |
| Frequency tolerance | Frequency selected (from ±1.5 Hz to ±5 Hz configurable) |
| OUTPUT and INVERTER OUTPUT |
| Rated power | 3000 VA |
| Active power | 2700 W |
| Number phases | 1 |
| Crest factor (Ipeak/Irms) | 3 : 1 |
| Waveform | Sinusoidal |
| Frequency | Selectable: 50 Hz or 60 Hz or self-learning |
| Voltage distortion with non-linear load | <4% |
| Voltage distortion with linear load | <2% |
| OVERLOAD TIMES |
| Load = 150% | 1 sec. |
| Load = 125% | 5 sec. |
| BATTERIES |
| Type | VRLA AGM maintenance-free lead based; Supercaps |
| Typical recharge time | 2-4 h |
| ENVIRONMENTAL |
| Color | Black |
| Communication | USB / DB9 with RS232 and contacts / Slot for communications interface |
| Accessories provided | Power cable, IEC-IEC cable, USB cable, safety manual, quick start guide |
| Surge capability | 300 J |
| Marks | CE, GS/NEMKO |
| Line-Interactive/Smart Active efficiency | 98% |
| Noise (at 1 m) | <40 [bBA] (ECO Mode) |
| Operating temperature | 0 °C – +40 °C |
| Relative humidity | 5-95% non-condensing |
| Standards | European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility — Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant — Classification in accordance with IEC 62040-3 VFI – SS – 111 |
| DATA |
| Weight | 28 kg |
| Dimensions (h w d) | 333x190x446 mm |